| Technical Specifications | |
|---|---|
| Model | M1-AIM-300 |
| Standard | EN 54-18, EN 54-17 |
| Power Supply | 27 V |
| Standby Consumption | 1 mA @ 27 V |
| Alarm State Current | 1.6 mA @ 27 V |
| Operating Temperature | −10 °C to +70 °C |
| Humidity | ≤95% RH, non-condensing |
| Maximum Line Voltage | 28 V |
| Minimum Line Voltage | 15 V |
| VSO max | 6 V |
| VSO min | 2 V |
| VSC max | 6 V |
| VSC min | 2 V |
| IC max | 400 mA |
| IS max | 600 mA |
| IL max | 8 mA |
| ZC max | 0.5 Ω |
| Dimensions | 90 × 55 × 20 mm |
| Weight | 60 g |
Addressable Input Module
M1-AIM-300
SKU
M1-AIM-300
Categories: Addressable Fire Alarm Systems, Modules
The M1-AIM-300 is a reliable and compact input module designed for addressable fire alarm systems to transmit signals from non-addressable devices to the control center. Its loop-powered technology requires no external power supply, allowing for easy integration within the loop and offering high performance in commercial and industrial applications.