Technical Specifications | |
---|---|
Model | I1-AIS-300 |
Compatibility | EN 54-17 |
Operating Voltage | 27 V |
Maximum Normal Consumption | 120 μA @ 27 V |
Operating Temperature | -10 °C/ 70 °C |
Humidity | 95% (Without Condensation) |
Maximum Line Voltage | 28 V |
Minimum Line Voltage | 15 V |
Max Voltage Isolated by Device (VSO Max) | 6 V |
Min Voltage Isolated by Device (VSO Min) | 2 V |
Max Voltage to Reconnect Device (VSC Max) | 6 V |
Min Voltage to Reconnect Device (VSC Min) | 2 V |
Max Continuous Current with Switch Closed (IC Max) | 400 mA |
Max Switching Current (IS Max) | 600 mA |
Max Leakage Current (IL Max) | 8 mA |
Max Series Impedance with Switch Closed (ZC Max) | 0.5 kΩ |
Dimensions | 25×55×95 mm |
Weight | 45 gr |
Isolator Module I1-AIS-300
Categories: Addressable Fire Alarm Systems, Modules
The I1-AIS-300 is an isolator module designed to protect the circuits of addressable control panels from short circuits. When a short circuit occurs within a loop, this module isolates the affected section, prevents other components from being damaged, and ensures the system continues to operate without interruption.