| Technical Specifications | |
|---|---|
| Model | I1-AIS-300 |
| Compatibility | EN 54-17 |
| Operating Voltage | 27 V |
| Maximum Normal Consumption | 120 μA @ 27 V |
| Operating Temperature | -10 °C/ 70 °C |
| Humidity | 95% (Without Condensation) |
| Maximum Line Voltage | 28 V |
| Minimum Line Voltage | 15 V |
| Max Voltage Isolated by Device (VSO Max) | 6 V |
| Min Voltage Isolated by Device (VSO Min) | 2 V |
| Max Voltage to Reconnect Device (VSC Max) | 6 V |
| Min Voltage to Reconnect Device (VSC Min) | 2 V |
| Max Continuous Current with Switch Closed (IC Max) | 400 mA |
| Max Switching Current (IS Max) | 600 mA |
| Max Leakage Current (IL Max) | 8 mA |
| Max Series Impedance with Switch Closed (ZC Max) | 0.5 kΩ |
| Dimensions | 25×55×95 mm |
| Weight | 45 gr |
Isolator Module I1-AIS-300
Categories: Addressable Fire Alarm Systems, Modules
The I1-AIS-300 is an isolator module designed to protect the circuits of addressable control panels from short circuits. When a short circuit occurs within a loop, this module isolates the affected section, prevents other components from being damaged, and ensures the system continues to operate without interruption.
2-Year Warranty
7/24 Technical Support
100% Customer Satisfaction
Related Products
Related Products
- Addressable Fire Alarm Systems
W1-ACP-310 WISE 10-Loop Addressable Control Panel
- Addressable Fire Alarm Systems
W2-ARP-300 Addressable Repeater Panel
- Addressable Fire Alarm Systems
F2-ASF-300 Addressable Sounder/Flasher
- Addressable Fire Alarm Systems
S2-AMD-300 Addressable Smoke/Heat Multi-Sensor Detector






