Technical Specifications | |
---|---|
Model | I1-AIS-350 |
Operating Voltage | 27 V |
Maximum Normal Consumption | 350 μA @ 27 V |
Operating Temperature | -10°C/ 70°C |
Humidity | 95% (Without Condensation) |
Maximum Line Voltage | 28 V |
Minimum Line Voltage | 15 V |
Max Voltage Isolated by Device (VSO Max) | 3.4 V |
Min Voltage Isolated by Device (VSO Min) | 0 V |
Max Voltage to Reconnect Device (VSC Max) | 27 V |
Min Voltage to Reconnect Device (VSC Min) | 3.5 V |
Max Continuous Current with Switch Closed (IC Max) | 7.25 mA |
Max Switching Current (IS Max) | 400 mA |
Max Leakage Current (IL Max) | 5 mA |
Max Series Impedance with Switch Closed (ZC Max) | 4 kΩ |
Dimensions | 25×55×95 mm |
Weight | 45 gr |
I1-AIS-350 Isolator Module
Categories: Addressable Fire Alarm Systems, Modules
The I1-AIS-350 Isolator Module is designed to protect addressable fire alarm system circuits against short circuits. When a short circuit occurs within a loop, the module automatically isolates the affected section, preventing damage to other devices and ensuring uninterrupted system operation. Its essential role in maintaining system integrity makes the I1-AIS-350 a vital component in enhancing the safety and reliability of modern fire alarm networks.
2-Year Warranty
7/24 Technical Support
100% Customer Satisfaction
Related Products
Related Products
-
Addressable Fire Alarm Systems
W1-ACP-310 WISE 10-Loop Addressable Control Panel
-
Addressable Fire Alarm Systems
S6-ACP-300 Addressable Resettable Manual Call Point
-
Addressable Fire Alarm Systems
S2-ARD-300 Addressable Rate-of-Rise Heat Detector
-
Addressable Fire Alarm Systems
H2-AHP-300 Handheld Programmer