| Technical Specifications | |
|---|---|
| Model | M1-AOM-300 |
| Standard | EN 54-18, EN 54-17 |
| Power Supply | 27 V |
| Standby Consumption | 1 mA @ 27 V |
| Alarm State Current | 1.6 mA @ 27 V |
| Output Relay | 30 V, 2 A |
| Operating Temperature | −10 °C to +70 °C |
| Humidity | ≤95% RH, non-condensing |
| Maximum Line Voltage | 28 V |
| Minimum Line Voltage | 15 V |
| VSO max | 6 V |
| VSO min | 2 V |
| VSC max | 6 V |
| VSC min | 2 V |
| IC max | 400 mA |
| IS max | 600 mA |
| IL max | 8 mA |
| ZC max | 0.5 Ω |
| Dimensions | 90 × 55 × 20 mm |
| Weight | 60 g |
Addressable Output Module
M1-AOM-300
SKU
M1-AOM-300
Categories: Addressable Fire Alarm Systems, Modules
The M1-AOM-300 is a reliable addressable output module designed in compliance with EN 54-18 and EN 54-17 standards. It operates without the need for an external power supply and is installed on the loop together with detectors, manual call points, sounders, and other connected devices. The module is responsible for transmitting commands from the addressable control panel to non-addressable equipment, ensuring smooth integration and efficient fire alarm system operation.
With its compact size, low power consumption, and wide operating temperature range, the M1-AOM-300 provides dependable performance in both residential and commercial environments.
2-Year Money-Back Guarantee
7/24 Technical Support
100% Customer Satisfaction
Related Products
Related Products
Addressable Optical Smoke Detector
S6-ASD-300Addressable Rate-of-Rise Heat Detector
S6-ARD-300Handheld Programmer
H2-AHP-300